CITEL PRODUCTS
TYPE 2 AC SURGE PROTECTOR - 3-PHASE+N
DS44-280/G

- Type 2 AC Multipolar surge protector
- In : 20 kA
- Imax : 40 kA
- Pluggable Module
- Remote signaling option
Discription
Electrical Properties
Mechinical Properties
Discription
Used mainly for primary protection of single and 4- phase networks at the main electrical panel. They provide common-mode or common and differential mode. This SPD is based on high energy varistor equipped with thermal disconnector and failure indicator, to comply with standards. The DS40 surge protectors are designed to be used in a multipolar configuration to protect single-phase, 3-phase or 3-phase+Neutral AC networks.They are sometimes associated with dedicated N/PE surge protector based on gas tube technology.
Electrical Properties
SPD type | 2 | |
Network | 230/400 V 3-phase+N | |
AC system | TT-TNS | |
Nominal line voltage | Un | 230 Vac |
Max. AC operating voltage | Uc | 280 Vac |
Temporary Over Voltage (TOV) Charasteristics – 5 sec. Without disconnection | UT | 335 Vac withstand |
Temporary Over Voltage (TOV) Charasteristics – 120 mn Without disconnection or with safety disconnection | UT | 440 Vac disconnection |
Temporary Over Voltage N/PE (TOV HT) Without disconnection or with safety disconnection | UT | 1200 V/300A/200 ms withstand |
Residual Current Leakage current to Ground | Ipe | None |
Operating current Continious current at Uc | Ic | 0.5 mA |
Follow current | If | None |
Nominal discharge current 15 x 8/20 µs impulses | In | 20 kA |
Max. discharge current max. withstand @ 8/20 µs by pole | Imax | 40 kA |
Total Maximum discharge current max. total withstand @ 8/20 µs | Imax Total | 40 kA |
Connection mode(s) | L/N and N/PE | |
Protection mode(s) | Common/Differential mode | |
Residuel voltage at 5 kA @ 5 kA (8/20µs) | Up-5kA | 0.9 kV |
Protection level L/N @ In (8/20µs) | Up L/N | 1.3 kV |
Protection level N/PE @ In (8/20µs) | Up N/PE | 1.5 kV |
Residual voltage at 10 kA @ 8/20µs | Up-10kA | 1.1 kV |
Admissible short-circuit current | Isccr | 25 000 A |
Mechinical Properties
Technology | MOV+GDT | |
SPD configuration | 3-phase+Neutral | |
Connection to Network | By screw terminals: 2.5-25mm² / by bus | |
Format | Plug-in modular box | |
Mounting | Symmetrical rail 35 mm (EN 60715) | |
Housing material | Thermoplastic UL94 V-0 | |
Operating temperature | Tu | -40/+85°C |
Protection rating | IP20 | |
Failsafe mode | Disconnection from AC network | |
Disconnection indicator | 1 mechanical indicator by pole | |
Spare module(s) | DSM40-280+DSM40G-600 | |
Remote signaling of disconnection | option DS44S-280/G: output on changeover contact | |
Dimensions | See diagram | |
Weight | 0.325 kg |